Motorola Releases New ACE3600 Software - Wednesday, March 24, 2010
Motorola announces the release of the following new ACE3600 software:
• M-OPC V3.10
• ACE3600 DNP Plus Master Driver V5.10 CD
• ACE3600 DNP Plus Salve Driver V5.10 CD
• ACE3600 IEC 60870-5-101 Salve Driver V2.00 SP1 CD
WHAT'S NEW IN M-OPC V3.10 (COMPARED TO V3.00):
New Features:
- It is now possible to update the Ladder application data base using the M-OPC Configuration Tool without reinstalling a new version of Motorola OLE Process Control (M-OPC).
- 2 new System Items are supported for each defined RTU:
Communication Status - Status of the last communication with the RTU (succeeded, failed or no communication queries occurred).
Last Update Time - Time of last communication with RTU (the count of minutes from the beginning of the current day).
Problems Corrected:
- The M-OPC client receives a periodic OnDataChange event from the M-OPC server (according to the group scan rate) only if the M-OPC item Value or M-OPC item Quality is changed.
- Installation setup - The password for the MDLC driver is clearly displayed on screen when entered.
Known Issues:
- When the M-OPC server fails to initialize the MDLC driver, it displays the following message: "Failed to create OPC local connection."
- When the M-OPC server starts, all items' quality are displayed as "BAD" until the server retrieves their real state from the RTUs.
- When the M-OPC server is down and two clients or more try connecting to it simultaneously, the M-OPC might not start up properly and the connections may fail. Clients should connect one at a time to ensure proper connection.
WHAT'S NEW IN ACE3600 DNP PLUS MASTER DRIVER V5.10 (COMPARED TO V5.00):
Enhancements:
- An option to the UnsolM parameter Added.
- Updated documents and the template projects.
Problems Corrected:
- Time synchronization issue.
- Events milliseconds - in the Events Table was always zero.
WHAT'S NEW IN ACE3600 DNP PLUS SLAVE DRIVER V5.10 (COMPARED TO V5.00):
New Features:
- "DI events limited" mode added.
- Support the UTC time base in accordance with TB2007-01a.
- A new UCALL – DsretE added.
Enhancements:
- Up to 30,000 Binary Input points.
- Expanded DSdefv/DS<n>dfv UCALL parameters options to objects 30 and 40.
- Updated documents and template projects.
- Problems corrected.
- When the SnapSh parameter was set to 0 – The Class 0 data was sometimes wrong.
- ALcnTO was limited to 655, instead of 65535.
WHAT'S NEW IN ACE3600 IEC SLAVE DRIVER V2.00 SP1 (COMPARED TO V2.00):
Problems Corrected:
- The demo application has been modified since it could not be upgraded to newer STS versions.
FURTHER INFORMATION
Please contact Adam Polak, Product Operations - Asia Pacific
Tel: +61 3 9847 7593
Email: Adam.Polak@motorola.com